Setup / installation inductive sensors

Functional principle

To rule out unintentional interference of the measuring field and to achieve maximum sensing distances, it is required to follow the mounting instructions and to maintain the specified minimum distances. If the minimum distances are undercut, a reduction of the sensing distances is expectable. A sensor test directly at the application is recommended.

Mounting instructions for cylindrical forms:

 


Shielded (flush) mounting
Sensor may be mounted flush in a metal plate. Choice of carrier material can have an influence on sensing distance.

 


Unshielded (non-flush) mounting
There must be a space equal to the diameter of the sensing head, with no metal interference. Following this rule the electrical field strength is less attenuated, which enables a larger sensing distance.

 

Quasi shielded mounting
When mounted in ferromagnetic material these sensors require a space (x) behind the active area that is free of metal. Sensors can be installed shielded (flush) when mounted in non ferrous materials (colored metals etc.). Always read and follow the installation instructions for distance measuring sensors.

 

Opposite mounting
Minimum distances must be observed to prevent oppositely positioned sensors from affecting each other.

 

Maximum installation torque

To avoid damage to the proximity switches during mounting, the default torque value should not be exceeded. Reduce torque values by 30 % at the sensor’s face.

 

 

Maximum installation torque

To avoid damage to the proximity switches during mounting, the default torque value should not be exceeded. Reduce torque values by 30 % at the sensor’s face.

 

Cable dimensions